Last Uploaded: April, 2011

KAJIMA AKASAKA ANNEX

Architectural DataFeaturesCasbee ScoreTechnical DetailsBack to Building List建物リストに戻る

Facade Engineering

click to enlarge
Window perimeter's thermal environment and energy performance projection
Window perimeter's thermal environment and energy performance projection Window perimeter's cross-sectional temperature distribution data    

High-performance Low-E glass was adopted to achieve often contradicting requirements: superb environmental performance and excellent views from the building. The multi-layered glass structure consists of heat-absorbing glass (12mm) on the exterior and floating glass (8mm) on the inside, with air space (12mm) in between. Low-E sputter coating was applied on the air space side of the floating glass, ensuring minimum heat transfer from the outside while allowing a clear view from the inside of the building.

Task & Ambient Air Conditioning System

click to enlarge
Task & Ambient Air Conditioning System
Task & Ambient Air Conditioning System    

The task and ambient air-conditioning system is based on the concept of air-conditioning on demand, i.e., air-conditioning only the necessary areas. The system adopted for this building consists of an ambient air conditioner that gently air-conditions the entire room and supplies outside air, as well as a task air conditioner in each module. The system allows office workers to control the temperature from their seats according to their preferences using the task air conditioner.

Eco-Module

click to enlarge
Hybrid sensor and free address wireless remote thermometer
Hybrid sensor and free address wireless remote thermometer Energy saving control system with occupancy sensor  

A hybrid sensor was provided in each module in the office space. This sensor consists of 3 separate sensors. The occupancy sensor detects non-occupancy in the room and switches off the lights and air conditioners to prevent wasteful energy consumption. The wireless remote thermometer detects the temperatures at locations close to people and transmits the information to the free address hybrid sensor. The luminance sensor detects the light intensity in the room and automatically controls the luminance of lights to save energy.

Universal Comfort

click to enlarge
Universal comfort concept
Universal comfort concept Air flow pattern visualization  

Localized air flow and sudden temperature changes in the multi-split heat pump system may create user discomfort. To solve this problem, an air diffuser was developed to allow users to adjust the air flow and diffusion mode according to individual preference. The air velocity in task areas was determined based on testing and the effectiveness of the system has been continuously verified by monitoring the rate of actual usage.

Natural Ventilation

click to enlarge
Natural ventilation system
Natural ventilation system    

As a way to effectively utilize natural energy, the building has a natural ventilation mechanism that uses the outside air when appropriate. The building's passive natural ventilation system uses temperature differences to create air movement vertically through the interior staircases. According to the post-construction testing of the natural ventilation system, it was verified that natural energy accounted for approximately 10% of intermediate load processing.

Previous BuildingPrevious Building Next BuildingNext Building
These cases are described based on assessment results obtained using CASBEE.
CASBEE is a method for rating the environmental performance of buildings using Building Environmental Efficiency (BEE) as an indicator, which is based on the results of separate scores obtained for Q-1~Q-3 (Quality) and LR-1~LR-3 (Load Reduction).